Abstract: . . . Renewable Energy Lab Mentor's Name: Andy Walker Phone: (303)-384-7411 e-mail Address: andy_walker@nrel.gov Presenter's Name: Mailing Address: City/State/Zip: Phone: email Address: Brittany Walker PO Box 4344 Boulder, CO 80306 (303)-448-9187 walkerba@angelfire.com Brittany Walker, 2001 iii Abstract Renovation of the Photovoltaic-Diesel Generator Hybrid System at Natural Bridges National Monument. BRITTANY WALKER (University of Colorado, Boulder, Colorado 80309), Andy Walker (National Renewable Energy Laboratory, Golden, Colorado, 80401). In 1979 a large 93 kW photovoltaic-diesel generator hybrid . . . . . . Bridges using HOMER. Component PV (kW) Generator (kW) Battery (kWh) Inverter (kW) Fuel Consumption (L/yr) Generator Hours (hr/yr) Capital Cost Net Present Cost Optimum 40 60 400 40 20,073 1165 $110,133 $ Brittany Walker, 2001 18 Table 5. Results from modeling the addition of 5 kW PV and 10 kW PV at the system at Natural Bridges using HOMER. Component PV (kW) Generator (kW) Battery (kWh) Inverter (kW) Fuel Consumption (L/yr) Generator Hours (hr/yr) Capital Cost Net Present Cost Adding 5 kW PV 45 60 400 40 17,655 1165 $ $ Adding 10 kW PV 50 60 400 40 15,413 1197 Brittany Walker, 2001 19 . . . . . . Brittany Walker, 2001 iii Abstract Renovation of the Photovoltaic-Diesel Generator Hybrid System at Natural Bridges National Monument. BRITTANY WALKER (University of Colorado, Boulder, Colorado 80309), Andy Walker (National Renewable Energy Laboratory, Golden, Colorado, 80401). In 1979 a large 93 kW photovoltaic-diesel generator hybrid system was installed as the only source of power for Natural Bridges National Monument. As the components in the system have aged the performance of the system has declined by more than 50% despite its upgrade in 1992. Natural Bridges has enlisted the help of the . . . . . . (hr/yr) Capital Cost Net Present Cost Optimum 40 60 400 40 20,073 1165 $110,133 $ Brittany Walker, 2001 18 Table 5. Results from modeling the addition of 5 kW PV and 10 kW PV at the system at Natural Bridges using HOMER. Component PV (kW) Generator (kW) Battery (kWh) Inverter (kW) Fuel Consumption (L/yr) Generator Hours (hr/yr) Capital Cost Net Present Cost Adding 5 kW PV 45 60 400 40 17,655 1165 $ $ Adding 10 kW PV 50 60 400 40 15,413 1197 Brittany Walker, 2001 19 . . . . . . Bridges using HOMER. Component PV (kW) Generator (kW) Battery (kWh) Inverter (kW) Fuel Consumption (L/yr) Generator Hours (hr/yr) Capital Cost Net Present Cost Optimum 40 60 400 40 20,073 1165 $110,133 $ Brittany Walker, 2001 18 Table 5. Results from modeling the addition of 5 kW PV and 10 kW PV at the system at Natural Bridges using HOMER. Component PV (kW) Generator (kW) Battery (kWh) Inverter (kW) Fuel Consumption (L/yr) Generator Hours (hr/yr) Capital Cost Net Present Cost Adding 5 kW PV 45 60 400 40 17,655 1165 $ $ Adding 10 kW PV 50 60 400 40 15,413 1197 Brittany Walker, 2001 19 . . . --3000,5,300,3211,26919
|